Ex AD
Features/Options
- Available as Ex "e" increased safety and
Ex "i" intrinsic safety versions - Ex zone 1 and 2, as well as
21 and 22 - Junction or terminal box devices
- 3 different enclosure sizes
85 x 85 mm; 115 x 115 mm; 145 x 145 mm - Polyester resin enclosure
- PU foam gaskets
Product image

Technical Data
| Standards | EN 60079-0; EN 60079-7; EN 60079-11; EN 60079-18; EN 61241-0; EN 61241-1 |
|---|---|
| Enclosure | glass fibre-reinforced polyester resin |
| Degree of protection | IP 66 per IEC/EN 60529 |
| Connection | screw terminals Ex AD 85 MK: 4 or 5, Ex AD 115 MK: 8, Ex AD 145 MK: 8 |
| Cable section | Ex AD 85: max. 4 mm², Ex AD 115: max. 6 mm², Ex AD 145: max. 10 mm² (incl. conductor ferrules), single-wire |
| Cable entry | M20 x 1.5, M25 x 1.5, M32 x 1.5 |
| Ue | Ex AD 85 FK: max. 550 V without fuse, Ex AD 115 FK: max. 750 V without fuse, Ex AD 145 FK: max. 750 V without fuse, max. 250 V or 550 V depending on the fuse Ex AD ... MK: max. 1100 V without fuse, max. 550 V with fuse |
| Rated operating current/voltage |
Ex AD 85: 25 A / 550 VAC, Ex AD 115: 32 A / 750 VAC, Ex AD 145: 44 A / 750 VAC |
| Temperature class | T6 / T5 |
| Ambient temperature | Ex e: T6: - 40 °C ... + 40 °C, T5: - 40 °C ... + 55 °C Ex i: - 40 °C ... + 75 °C, - 50 °C with special cable glands |
| Ex marking Ex AD e: |
II 2G Ex em II T6, T5, T4 II 2D Ex tD A21 IP66T80°C, T95°C, T130°C |
| Ex marking Ex AD i: |
II 2G Ex ia/ib IIA, IIB, IICT6,T5 II 2D Ex tD A21 IP66T80°C, T95°C, T130°C |
| Approvals | PTB 10 ATEX 1019 X |





II 2G Ex em II T6, T5, T4