Safety relay module SRM 21 Multi

Features/Options

  • Enclosure width: 22.5 mm
  • 2 NC contact combination connectable
  • Feedback circuit
  • 2 enabling paths potential-free
  • 1 auxiliary output
  • Manual or automatic start
  • LED indicator for switching condition
  • PL e, SIL CL 3

Product image

 

Technical data

Standards IEC/EN 60204 -1, EN 60947-5-1,
EN 61508, EN ISO 13849-1;
EN 60947-5-3/PDF-M
Enclosure Polyamid PA 6.6 V0 black;
DIN rail mounting
per EN 50022
Connection screw terminals
Cable section 1x 2.5 mm²/2x 1.5 mm² strand including conductor ferrules,
1x 4 mm²/2x 2.5 mm² massive
Degree of protection Enclosure IP 40,
terminals IP 20 as per IEC 60 529,
contact protection
per VBG 4
Rated operating voltage Ue 24 VDC -20%, +25 %
Power consumption <3 W
Inputs 2 NC,1 feedback input,
1 start input
Outputs 2 enabling paths, 1 auxiliary output
Utilisation category AC-1; DC-1
Rated operating
current/voltage Ie/Ue
Enabling paths
6 A/250 VAC; 6 A/24 VDC
Max. output current
auxiliary S11, S21, S31
output Ia
50 mA
Short-circuit protection
Supply voltage Ue
2 A gL/gG D-fuse
Enabling paths 6 A gL/gG D-fuse
Safety-related data control category 4 per EN 954-1,
PL e per EN ISO 13849-1,
SIL 3 per EN 61508
Release delay ≤125 ms
Mech. life >10 million switching cycles
LED display 4: Operation, fault,
inputs A and B
Degree of pollution 2 per EN 50178, DIN VDE 0110
Overvoltage category III
Ambient temperature -25 °C … +55 °C
Storage/shipping temp. -25 °C ... +75 °C
Shock resistance 10g
TM max. 20 years
Approvals BRD