ZS 75 S

Particularités/options

  • Corps métal
  • 2 ou 4 contacts
  • Protection 2 x 100 m
  • Réarmement par bouton poussoir (VD) ou par clé (VS) possible
  • Available without unlocking mechanism (per DIN EN 60947-5-1)
  • fonction "traction et rupture de câble"
  • Indicator lamps for various voltages are indicated in chapter accessories in the appendix
  • Voyant d'état (Led) disponible sur demande
  • Version with Dupline or Dupline Safe available
  • Disponible en version Atex

Product image

 

Technical data

Standards EN ISO 13849-1;
IEC/EN 60947-5-1;
IEC/EN 60947-5-5; EN 418
Enclosure aluminium die-cast, enamel finish
Cover aluminium die-cast, enamel finish
Degree of protection ZS 75 S VD: IP 65
ZS 75 S VS: IP 54
ZS 75 S VZ: IP 67
to IEC/EN 60529
Contact material silver
Switching elements change-over contact with double break or 2 NC/2 NO or 4 NC contacts
Switching system snap action, positive break
NC contacts Zwangsöffnung
Connection screw terminals
Cable section max. 2.5 mm2
(incl. conductor ferrules)
Cable entry 2 x M25 x 1.5
B10d (10% Load) 200.000
TM max. 20 years
Uimp 6 kV
Ui 400 V
Ithe 6 A
Utilisation category AC-15
Ie/Ue 6 A/400 VAC
Max. fuse rating 6 A gL/gG D-fuse
Ambient temperature –25 °C … +70 ºC
Mech. life > 100.000 operations
Indicator lamp as option
Max. wire length 2 x 100 m
Features wire pull and breakage detection
Approvals BRD